HOSPITAL SOUNDSCAPE: ACOUSTICS EVALUATION IN NEONATAL INTENSIVE CARE UNIT (NICU) ROOM OF A NATIONAL HOSPITAL IN JAKARTA, INDONESIA

Authors

  • SARWONO R. Sugeng Joko
  • WULANDHARI Rezzy Yolanda
  • HABIBA Sofiya
  • AZZAHRA Iva Rofiatun Nisa
  • UTAMI Sentagi Sesotya
  • HARDJOPRAWITO Tri Juda Airlangga
  • SEDONO Rudyanto

:

https://doi.org/10.9744/dimensi.43.2.101-106

Keywords:

Acoustic, soundscape, neonatal intensive care unit.

Abstract

Acoustics comfort in a room is one of the most important building physics aspect that should be observed. in public spaces like hospital, especially in an intensive care unit such as NICU. Researches on the acoustic conditions of NICU in Indonesia are still limited. The acoustical study conducted in this research is using objective, subjective, and simulation methods based on soundscape concept with the concern on the nurse’s perception. This research was conducted at a national hospital in Jakarta. According to National Standardization Agency of Indonesia (SNI) and World Health Organization (WHO), the suitable sound pressure level (SPL) for noise in patient’s room is 35 dBA. From the study, it was found that the equivalent SPL value exceeded the standard. Soundscape in NICU can be improve with the addition of curtain on the incubator’s side, installation of glass partition, and ceiling absorber in the nurse station area. The result of simulation showed that the SPL in the room decreased with average value 8.9 dBA for sound source alarm ventilator and 8.2 dBA for sound source medical officer conversations. And the speech transmission index (STI) increased from “bad” to “good” range became “fair” to “excellent” range.

Downloads

Download data is not yet available.

References

“Absorption Coefficients α of Building Materials and Finishes”. [Online]. Available. http://www. sengpielaudio.com/calculator-RT60Coeff.htm. [Accessed: 30 - June – 2016]. [CrossRef]

”Absorption Coefficients”. [Online]. Available. http://www.acoustic.ua/st/web_absorption_data_eng.pdf. [Accessed: 30 - June - 2016]. [CrossRef]

Indonesian National Standard. National (2000). SNI 03-6386-2000. Jakarta: Standardization Agency of Indonesia. [CrossRef]

International Organization for Standardization (2003). ISO 9921:2003 – Ergonomics – Assessment of Speech Communication. [CrossRef]

International Organization for Standardization (2012). ISO 3383-3: 2012 - Acoustics -- Measurement of Room Acoustic Parameters; Part 3: Open Plan Offices. [CrossRef]

M.Vorlander. (2007). CERN Document Server. [Online]. Available. https://cds.cern.ch/record/ 1251519/files/978-3-540-48830-9_BookBack Matter.pdf [Accessed: 25 - June - 2016]. [CrossRef]

“NICU/PICU”. [Online]. Available. http://bunda.co. id/rsiabundajakarta/id_ID/facilities-and-services/support-facilities/nicupicu/. [Accessed: 30 – June – 2016] [CrossRef]

Ryherd, E. E., Waye, K. P. & Ljungkvist, L. (2007). Characterizing Noise and Perceived Work Environment in A Neurological Intensive Care Unit. J. Acoust. Soc. Am., 123(2), p.1. [CrossRef]

WHO, Guidelines Values for Community Noise. [Online]. Available. http://www.who.int/docstore/peh/noise/Comnoise-4.pdf [Accessed: 21 Maret 2016]. [CrossRef]

Downloads

Published

2016-12-01

How to Cite

R. Sugeng Joko, S., Rezzy Yolanda, W., Sofiya, H., Iva Rofiatun Nisa, A., Sentagi Sesotya, U., Tri Juda Airlangga, H., & Rudyanto, S. (2016). HOSPITAL SOUNDSCAPE: ACOUSTICS EVALUATION IN NEONATAL INTENSIVE CARE UNIT (NICU) ROOM OF A NATIONAL HOSPITAL IN JAKARTA, INDONESIA. Dimensi: Journal of Architecture and Built Environment, 43(2), 101-106. https://doi.org/10.9744/dimensi.43.2.101-106